Description
Technical specifications | Type ANFR PVC G1 |
Sensor element: | Pt100 (TK3850), Pt500 (TK3850), Pt1000 (TK3850) Ni1000 (TK5000), Ni1000 (TK6180) |
Sensor accuracy: | Pt: DIN Class B (-200°C to +850°C), DIN 60751 DIN Class A (-90°C to +300°C), DIN 60751 1/3 DIN Class B (-50°C to +150°C), DIN 60751 |
Ni: Class B (-50°C to +300°C), DIN 43760 Class A (-50°C to +300°C), DIN 43760 |
|
Application temperature: | -30°C to +105°C |
Connections: | 2-wire, 3-wire, 4-wire |
Measuring current: | 100Ω → 1mA; 500 Ω → 0.5mA; 1000Ω → 0.3mA |
Connecting cable: | PVC, cross section 0.22mm² |
Cable diameter: | 5mm |
Cable length: | Depending on customer specifications |
Housing: | Contact body with radius R=30mm |
Protection class: | Only for dry applications |
Areas of application: | Building technology, ventilation technology, heating technology, process technology |
Options: | Measuring transducer of 4–20 mA or 0–10 V, variable cable lengths, connectors, other probe dimensions |
Datasheet |